Infrared camera
Updated 2026-10-27
Data records
- The survey covers electrical panels, switchgear, breakers, fuses and other high-load connection points such as drives, disconnects and controls, with the covers removed, since the camera cannot see through a closed cabinet or a solid metal bus tray.
- An infrared camera forms an image from the thermal radiation that surfaces emit and shows the apparent temperature at each point; in electrical inspection it reveals the abnormal heating that increased resistance at a contact surface produces while the equipment carries load.
- Because electrical components are mostly bare metal with low emissivity, absolute temperature readings from the camera are unreliable, so many thermographers run qualitative surveys that compare apparent temperatures between like components carrying like loads, or on the same equipment over time.
- Emissivity is a measure of how efficiently a surface radiates infrared energy, on a scale from a perfect mirror to a perfect absorber and radiator; polished metal sits at the low end and behaves as a mirror, while roughened, oxidized and painted surfaces sit high. The camera's emissivity setting is matched to the surface, and a patch of electrical tape on shiny metal gives a surface whose temperature the camera can read.
- Heat concentrated at one point, such as a switch contact, a connector or one end of a fuse, marks poor surface contact at that point, while heat along a whole conductor, or a fuse hot at both ends, marks an overloaded or undersized circuit or a phase imbalance.
- A radiometric camera stores a temperature value for every pixel so that the image can be measured and re-analyzed after the survey, whereas a non-radiometric imager shows only the thermal pattern.
- Reflected temperature is the radiation from the surroundings that a low-emissivity surface bounces into the camera; it is entered in the camera's settings, has less influence on high-emissivity surfaces, and can make a cool component appear hot or a warm one appear cold if it is not accounted for.
- Each suspected problem is documented in a report that carries the thermal image and a visible-light photograph of the equipment, and the saved images form a baseline for comparison in later maintenance; a new image after corrective action shows whether the repair succeeded.
- The equipment is imaged after it has warmed to a steady state under a meaningful share of its normal load, and the load is measured with a clamp meter or power quality analyzer, because an unbalanced load, an overload and a poor connection can produce similar thermal patterns.
Elsewhere in the family
- Infrared Thermographic Survey related entry on Electrical Testing Reference
Sources
- Electrical Testing Reference editorial taxonomy, Electrical Testing Reference editorial taxonomy of test methods, 2026-10 edition, Electrical Testing Reference. Held as: Own observation.
- Fluke article page, Using thermal imaging cameras for electrical inspections, web page edition, Fluke. Held as: Public page. Publisher page
- Fluke article page, Hot spot detection - what to look for, web page edition, Fluke. Held as: Public page. Publisher page
- Teledyne FLIR article page, How Does Emissivity Affect Thermal Imaging?, web page edition, Teledyne FLIR. Held as: Public page. Publisher page
Changelog (23 entries)
| Date | Revision | Change |
|---|---|---|
| 2026-10-27 | created (instr.infrared-camera.applications) | |
| 2026-10-27 | revised (instr.infrared-camera.applications) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.applications) | |
| 2026-10-27 | created (instr.infrared-camera.definition) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.definition) | |
| 2026-10-27 | created (instr.infrared-camera.delta-t) | |
| 2026-10-27 | revised (instr.infrared-camera.delta-t) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.delta-t) | |
| 2026-10-27 | created (instr.infrared-camera.emissivity) | |
| 2026-10-27 | revised (instr.infrared-camera.emissivity) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.emissivity) | |
| 2026-10-27 | created (instr.infrared-camera.patterns) | |
| 2026-10-27 | revised (instr.infrared-camera.patterns) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.patterns) | |
| 2026-10-27 | created (instr.infrared-camera.radiometric) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.radiometric) | |
| 2026-10-27 | created (instr.infrared-camera.reflected-temperature) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.reflected-temperature) | |
| 2026-10-27 | created (instr.infrared-camera.report) | |
| 2026-10-27 | revised (instr.infrared-camera.report) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.report) | |
| 2026-10-27 | created (instr.infrared-camera.under-load) | |
| 2026-10-27 | review_status unreviewed -> software_reviewed (instr.infrared-camera.under-load) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Infrared camera." Test Instrument Reference. 2026-10-27. https://www.testinstrumentreference.com/instruments/infrared-camera/.
Test Instrument Reference, Infrared camera (Oct. 27, 2026), https://www.testinstrumentreference.com/instruments/infrared-camera/.
@misc{etr-instruments-infrared-camera,
title = {Infrared camera},
howpublished = {\url{https://www.testinstrumentreference.com/instruments/infrared-camera/}},
organization = {Test Instrument Reference},
publisher = {Test Instrument Reference},
year = {2026},
note = {last substantive change 2026-10-27}
}{{cite web |title=Infrared camera |website=Test Instrument Reference |publisher=Test Instrument Reference |url=https://www.testinstrumentreference.com/instruments/infrared-camera/ |date=2026-10-27 |access-date=}}